DEMCO D213-2 PHOTOELECTRIC SMOKE DETECTOR

RM 70.00
- +
icon-bag Add to Cart
WHATSAPP

DEMCO Photoelelctric Smoke Detector D-213 with its new sensor design incorporates an internal pulsing LED and a photo-diode at an obtuse angle, is ideal for applications where slow-burning or smouldering fires are likely.

The D-213 has an advanced solid-state, low-voltage, surface-mount circuitry and are designed for 2-Wire installation using the D3X001 universal base. The detector head is installed into the base with a simple twist-lock action.

The 360-degree detector designed permits operation in open areas with air velocities form 0 to 300fpm.

A fine wire mesh extending between offsets ports in the exterior and interior walls screens insects from the chamber and obstructs light from passing directly to the interior part.


  • Certification/Listing-UL, CE and BSI.
  • Advanced detection and discrimination algorithms.
  • Advanced solid-state, low-voltage, surface-mount circuitry.
  • Suitable for the majority of application conditions.
  • Easy installation, testing and maintenance.
  • Sleek low-profile housing design.
  • Flashing LED in standby mode.
  • Robust and reliable sensor head.
  • Two red LEDs to allow 360-degree viewing.
  • A fine mesh insect screen protects the chamber area.
  • Optional/integrated heat detector for D213-2H and D213-2HL models.
  • ModelHeat Sensor SettingVolltage DC (Max./Min.)Standby Current (Max.)Alarm Current (12/24V)Surge Current (Max.)Start-up Time (Max.)Permissible Current (Max.)Cycle TimeBase Model No.Safety
    D-213-210.8 ~ 33V80µA22/55mA160µA30 Sec.80mA1-3 Sec.D32001UL/CE

  • Remarks: L = Remote LED indicator output / H = Heat Detector

    Smoke Sensitivity0.98-2.40% FT Obstruction (UL) ; 0.08-0.14 dB/m (EN)
    Ceiling Spacing50-foot rating for heat detector
    Temperature Range-10°C to 50°C
    Humidity0 to 95% RH, no condensation or icing
    Dimension (H x D)46 x 100mm with base
    Weight130g/set with base
    Smoke Sensitivity0.98-2.40% FT Obstruction (UL) ; 0.08-0.14 dB/m (EN)
    Ceiling Spacing50-foot rating for heat detector
    Temperature Range-10°C to 50°C
    Humidity0 to 95% RH, no condensation or icing
    Dimension (H x D)46 x 100mm with base
    Weight130g/set with base